top of page
CIVIL, STRUCTURAL & ARCHITECTURAL
COMPANY NAME:
TBC

System Description

DOORS, IRONMONGERY AND LOCKS

Doors:

The external and internal doors within the Substation building are as follows:

• All access and escape doors are provided with a panic exit bar

• All steel doors are connected to the main Substation earth

• All doors have an ID plate affixed; this indicates the traceable id reference, fire rating, security rating and blast rating.

• Generally, the doors are rated to 1-hour to 1.5-hour fire resistance. Transformer Bay doors are rated to 4-hour fire resistance.

Locking Mechanisms for access control:

UKPN area doors are provided with Cyber Locks as per UKPN EDS 07- 0120 requirements.

Customer area doors are provided with Solenoid lock system and Card Reader or Magnetic Shear Lock and Card Reader as indicated on the as-built drawings and door schedules.

For further details on the Door and Locking equipment Technical Data and Operating & Maintenance instructions, cross-refer to:

• Doors, Ironmongery and locks - refer to the Manufacturers’ Technical Literature

bottom of page